IVAR
IVAR SupeRAC
6 bar monobloc hot water boilers with flame reversal chamber and high efficiency
- Heating capacity
- 94 – 4,150 kW
- Energy
- Natural gas, LPG, diesel oil, biogas
- Efficiency
- 91 - 93%
IVAR · Boilers and steam generators
Superheated water generator with 3 flue gas passes
Technical data
Models
Technical data from the manufacturer's data sheet.
| Model | Unit | 120 | 180 | 230 | 320 | 400 | 500 | 600 | 800 | 1000 | 1200 | 1500 | 1750 | 2000 | 2500 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| PERFORMANCE AND HEAT OUTPUTS | |||||||||||||||
| Rated output [kW] | kW | 140 | 210 | 268 | 372 | 465 | 581.5 | 700 | 930 | 1,163 | 1,396 | 1,745 | 2,035 | 2,325 | 2,907 |
| Rated output [kcal/h x1000] | kcal/h x1000 | 120 | 180 | 230 | 320 | 400 | 500 | 602 | 800 | 1,000 | 1,200 | 1,500 | 1,750 | 2,000 | 2,500 |
| Furnace output [kW] | kW | 157 | 235 | 300 | 418 | 523 | 653 | 784 | 1,046 | 1,307 | 1,568 | 1,960 | 2,287 | 2,613 | 3,267 |
| Furnace output [kcal/h x1000] | kcal/h x1000 | 135 | 202 | 258 | 360 | 450 | 561 | 674 | 900 | 1,124 | 1,348 | 1,685 | 1,967 | 2,247 | 2,809 |
| HYDRAULIC AND COMBUSTION PARAMETERS | |||||||||||||||
| Combustion chamber pressure | mbar | 2 | 2.5 | 3 | 4.2 | 4.5 | 5 | 6 | 6.5 | 7 | 7 | 8 | 8.2 | 9 | 9.5 |
| Water-side pressure drop (Δt 15°C) | mbar | 3.7 | 8 | 13 | 24 | 11 | 17 | 12 | 18 | 20 | 30 | 37 | 30 | 40 | 45 |
| Water capacity | dm³ (L) | 335 | 410 | 410 | 780 | 780 | 875 | 964 | 1,189 | 1,485 | 1,696 | 2,455 | 2,750 | 3,100 | 4,200 |
| Maximum operating pressure | bar | 4.9 | |||||||||||||
| PHYSICAL DIMENSIONS | |||||||||||||||
| Overall outside width (A) | mm | 950 | 950 | 950 | 1,140 | 1,140 | 1,210 | 1,210 | 1,350 | 1,350 | 1,460 | 1,640 | 1,740 | 1,780 | 1,890 |
| Overall height (H) | mm | 1,235 | 1,225 | 1,225 | 1,430 | 1,430 | 1,510 | 1,510 | 1,670 | 1,670 | 1,770 | 1,940 | 2,050 | 2,080 | 2,190 |
| Overall outside length (Lt) | mm | 1,550 | 1,970 | 1,970 | 2,280 | 2,280 | 2,350 | 2,550 | 2,635 | 3,135 | 3,060 | 3,400 | 3,400 | 3,600 | 4,200 |
| Dimension C (width / front volume) | mm | 580 | 580 | 580 | 680 | 680 | 725 | 725 | 805 | 805 | 835 | 950 | 1,008 | 1,020 | 1,075 |
| Distance to furnace / flue axis (f) | mm | 375 | 425 | 425 | 477 | 477 | 487 | 487 | 578 | 578 | 568 | 570 | 685 | 695 | 720 |
| Distance between flow and return connections (i) | mm | 700 | 970 | 970 | 1,060 | 1,060 | 1,100 | 1,360 | 1,200 | 1,700 | 1,600 | 1,800 | 1,700 | 1,886 | 2,380 |
| CONNECTIONS AND WEIGHT | |||||||||||||||
| Flow / return connections (r - f) | DN | DN 65 | DN 65 | DN 65 | DN 80 | DN 80 | DN 100 | DN 100 | DN 125 | DN 125 | DN 150 | DN 150 | DN 200 | DN 200 | DN 200 |
| Drain connection (S) | DN | DN 25 | DN 25 | DN 25 | DN 25 | DN 25 | DN 25 | DN 25 | DN 25 | DN 25 | DN 40 | DN 40 | DN 40 | DN 40 | DN 40 |
| Flue diameter (Camino Ø) | mm | 220 | 220 | 220 | 250 | 250 | 250 | 250 | 350 | 350 | 400 | 450 | 450 | 500 | 500 |
| Empty weight | kg | 760 | 1,080 | 1,080 | 1,540 | 1,540 | 1,675 | 2,060 | 2,350 | 2,930 | 3,500 | 4,240 | 4,790 | 5,870 | 7,000 |
| Model | Unit | 120 | 180 | 230 | 320 | 400 | 500 | 600 | 800 | 1000 | 1200 | 1500 | 1750 | 2000 | 2500 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| PERFORMANCE AND HEAT OUTPUTS | |||||||||||||||
| Rated output [kW] | kW | 140 | 210 | 268 | 372 | 465 | 581.5 | 700 | 930 | 1,163 | 1,396 | 1,745 | 2,035 | 2,325 | 2,907 |
| Rated output [kcal/h x1000] | kcal/h x1000 | 120 | 180 | 230 | 320 | 400 | 500 | 602 | 800 | 1,000 | 1,200 | 1,500 | 1,750 | 2,000 | 2,500 |
| Furnace output [kW] | kW | 157 | 235 | 300 | 418 | 523 | 653 | 784 | 1,046 | 1,307 | 1,568 | 1,960 | 2,287 | 2,613 | 3,267 |
| Furnace output [kcal/h x1000] | kcal/h x1000 | 135 | 202 | 258 | 360 | 450 | 561 | 674 | 900 | 1,124 | 1,348 | 1,685 | 1,967 | 2,247 | 2,809 |
| HYDRAULIC AND COMBUSTION PARAMETERS | |||||||||||||||
| Combustion chamber pressure | mbar | 2 | 2.5 | 3 | 4.2 | 4.5 | 5 | 6 | 6.5 | 7 | 7 | 8 | 8.2 | 9 | 9.5 |
| Water-side pressure drop (Δt 15°C) | mbar | 3.7 | 8 | 13 | 24 | 11 | 17 | 12 | 18 | 20 | 30 | 37 | 30 | 40 | 45 |
| Water capacity | dm³ (L) | 335 | 410 | 410 | 780 | 780 | 875 | 1,020 | 1,189 | 1,485 | 1,696 | 2,455 | 2,750 | 3,100 | 4,200 |
| Maximum operating pressure | bar | 9.8 | |||||||||||||
| PHYSICAL DIMENSIONS | |||||||||||||||
| Overall outside width (A) | mm | 950 | 950 | 950 | 1,140 | 1,140 | 1,210 | 1,230 | 1,350 | 1,350 | 1,460 | 1,640 | 1,740 | 1,780 | 1,890 |
| Overall height (H) | mm | 1,235 | 1,225 | 1,225 | 1,430 | 1,430 | 1,510 | 1,530 | 1,670 | 1,670 | 1,770 | 1,940 | 2,020 | 2,080 | 2,190 |
| Overall outside length (Lt) | mm | 1,555 | 1,975 | 1,975 | 2,285 | 2,285 | 2,355 | 2,555 | 2,640 | 3,140 | 3,070 | 3,360 | 3,400 | 3,600 | 4,210 |
| Dimension C (width / front volume) | mm | 580 | 580 | 580 | 680 | 680 | 725 | 735 | 805 | 805 | 835 | 950 | 1,007 | 1,020 | 1,075 |
| Distance to furnace / flue axis (f) | mm | 378 | 427 | 427 | 479 | 479 | 488 | 488 | 579 | 578 | 575 | 576 | 680 | 715 | 725 |
| Distance between flow and return connections (i) | mm | 700 | 970 | 970 | 1,060 | 1,060 | 1,100 | 1,360 | 1,200 | 1,700 | 1,600 | 1,800 | 1,700 | 1,886 | 2,380 |
| CONNECTIONS AND WEIGHT | |||||||||||||||
| Flow / return connections (r - f) | DN | DN 65 | DN 65 | DN 65 | DN 80 | DN 80 | DN 100 | DN 100 | DN 125 | DN 125 | DN 150 | DN 150 | DN 200 | DN 200 | DN 200 |
| Drain connection (S) | DN | DN 25 | DN 25 | DN 25 | DN 25 | DN 25 | DN 25 | DN 25 | DN 25 | DN 25 | DN 40 | DN 40 | DN 40 | DN 40 | DN 40 |
| Flue diameter (Camino Ø) | mm | 220 | 220 | 220 | 250 | 250 | 250 | 250 | 350 | 350 | 400 | 450 | 450 | 500 | 500 |
| Empty weight | kg | 1,160 | 1,560 | 1,560 | 1,850 | 1,850 | 1,970 | 2,550 | 2,800 | 3,500 | 4,200 | 5,140 | 5,800 | 6,300 | 8,400 |
Downloads
We'll help you choose the model and send you the technical documentation and a proposal.
Boilers and steam generators
IVAR
6 bar monobloc hot water boilers with flame reversal chamber and high efficiency
IVAR
6 bar hot water boilers with twin stacked furnaces for wide modulation and redundancy
IVAR
High-efficiency hot water boilers with 3 flue gas passes and low NOx
IVAR
Very high-efficiency AISI 316L stainless steel condensing boilers for low temperatures
IVAR
Large industrial boilers with 3 true flue gas passes and low NOx
IVAR
Thermal oil boilers for high-temperature processes