Yazaki
Yazaki WFC-SC
Hot water-driven single-effect absorption chillers
- Cooling capacity
- 17.6 – 176 kW
- Energy
- Hot water
- Efficiency
- COP: 0.7
Thermax · Absorption chillers
Multi-energy absorption chillers driven by exhaust gas and hot water
Technical data
Models
Technical data from the manufacturer's data sheet.
| Model | Unit | E7 C3 | E7 C4 | E7 D1 | E7 D2 | E7 D3 | E7 D4 | E7 E1 | E7 E2 | E7 E3 | E7 E4 | E7 E5 | E7 E6 | E7 F1 | E7 F2 | E7 F3 | E7 G1 | E7 G2 | E7 G3 | E7 G4 | E7 G5 | E7 G6 | E7 H1 | E7 H2 | E7 J1 | E7 J2 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GENERAL DATA | ||||||||||||||||||||||||||
| Version / application | Multi-energy absorption chiller (exhaust gas + hot water) | |||||||||||||||||||||||||
| Installation location | Indoor | |||||||||||||||||||||||||
| Refrigerant / absorbent | Water (R718) / Lithium bromide (LiBr) | |||||||||||||||||||||||||
| Chilled water inlet / outlet temperature | °C | 12.0 / 6.0 | ||||||||||||||||||||||||
| Maximum allowable pressure, chilled water circuit | bar(g) | 8 | ||||||||||||||||||||||||
| Cooling water inlet temperature (tower) | °C | 27.0 | ||||||||||||||||||||||||
| Maximum allowable pressure, cooling water circuit | bar(g) | 8 | ||||||||||||||||||||||||
| CAPACITY AND HYDRAULIC CIRCUITS | ||||||||||||||||||||||||||
| Nominal cooling capacity | kW | 422 | 531 | 672 | 802 | 1,002 | 1,125 | 1,350 | 1,498 | 1,719 | 1,849 | 2,074 | 2,285 | 2,451 | 2,549 | 2,813 | 3,200 | 3,534 | 4,012 | 4,325 | 4,922 | 5,369 | 6,012 | 6,751 | 7,169 | 8,122 |
| Nominal cooling capacity (reference) | TR | 120 | 151 | 191 | 228 | 285 | 320 | 384 | 426 | 489 | 526 | 590 | 650 | 697 | 725 | 800 | 910 | 1,005 | 1,141 | 1,230 | 1,400 | 1,527 | 1,710 | 1,920 | 2,039 | 2,310 |
| Chilled water flow | m³/h | 60.1 | 75.8 | 95.8 | 114.4 | 143.1 | 161 | 193.2 | 214.6 | 246.1 | 264.6 | 296.8 | 326.9 | 350.5 | 364.8 | 402 | 457.7 | 505 | 573.6 | 618.7 | 703.8 | 768.2 | 859.8 | 965.6 | 1,025.7 | 1,161.6 |
| Cooling water flow (tower) | m³/h | 115 | 145 | 186 | 220 | 275 | 310 | 375 | 420 | 480 | 515 | 580 | 640 | 680 | 710 | 780 | 895 | 990 | 1,120 | 1,210 | 1,370 | 1,495 | 1,680 | 1,880 | 1,990 | 2,270 |
| FLUE GAS CIRCUIT (HEAT SOURCE 1) | ||||||||||||||||||||||||||
| Required heat input (exhaust gas) | kW | 185 | 224 | 270 | 343 | 420 | 471 | 557 | 620 | 711 | 759 | 862 | 948 | 1,043 | 1,078 | 1,183 | 1,324 | 1,458 | 1,659 | 1,789 | 2,045 | 2,263 | 2,537 | 2,823 | 2,918 | 3,332 |
| Flue gas inlet temperature range | °C | 350 – 600 | ||||||||||||||||||||||||
| Flue gas outlet temperature | °C | 170 | ||||||||||||||||||||||||
| HOT WATER CIRCUIT (HEAT SOURCE 2) | ||||||||||||||||||||||||||
| Required heat input (hot water) | kW | 185 | 246 | 358 | 392 | 500 | 563 | 693 | 777 | 885 | 962 | 1,056 | 1,167 | 1,195 | 1,281 | 1,423 | 1,651 | 1,824 | 2,046 | 2,225 | 2,493 | 2,669 | 2,997 | 3,371 | 3,788 | 4,203 |
| Hot water inlet temperature | °C | 90 | ||||||||||||||||||||||||
| Hot water outlet temperature | °C | 75 | ||||||||||||||||||||||||
| Maximum allowable pressure, hot water circuit | bar(g) | 8 | ||||||||||||||||||||||||
| ELECTRICAL DATA | ||||||||||||||||||||||||||
| Total electrical consumption | kVA | 10.1 | 10.1 | 11.2 | 11.2 | 14.8 | 14.8 | 16.9 | 19.1 | 19.1 | 21.3 | 21.3 | 21.3 | 26 | 26 | 28.2 | 29.6 | 29.6 | 29.6 | 29.6 | 37.5 | 37.5 | 37.5 | 38.5 | 40.7 | 40.7 |
| Supply voltage / supply conditions | V / Hz | 415V (±10%), 50Hz (±5%), AC III + neutral | ||||||||||||||||||||||||
| DIMENSIONS AND WEIGHTS | ||||||||||||||||||||||||||
| Length (L) | mm | 3,200 | 3,200 | 4,200 | 4,200 | 4,400 | 4,400 | 5,100 | 5,400 | 5,400 | 5,400 | 5,600 | 5,600 | 6,800 | 6,800 | 6,800 | 7,500 | 7,500 | 7,700 | 7,700 | 7,900 | 7,900 | 9,300 | 9,300 | 10,800 | 10,800 |
| Width (W) | mm | 2,900 | 2,900 | 3,000 | 3,000 | 3,200 | 3,200 | 3,500 | 3,600 | 3,600 | 3,600 | 3,800 | 3,800 | 4,000 | 4,000 | 4,000 | 4,300 | 4,300 | 4,500 | 4,500 | 4,800 | 4,800 | 4,900 | 4,900 | 5,000 | 5,000 |
| Height (H) | mm | 3,300 | 3,300 | 3,300 | 3,300 | 3,300 | 3,300 | 3,400 | 3,800 | 3,800 | 3,800 | 4,100 | 4,100 | 4,200 | 4,200 | 4,200 | 4,400 | 4,400 | 4,700 | 4,700 | 5,000 | 5,000 | 5,000 | 5,000 | 5,000 | 5,000 |
| Operating weight | kg | 10,000 | 11,000 | 12,500 | 13,500 | 16,500 | 17,500 | 19,000 | 22,500 | 23,500 | 24,500 | 28,000 | 31,000 | 35,200 | 37,000 | 39,500 | 50,000 | 52,000 | 62,000 | 65,000 | 77,000 | 80,000 | 88,000 | 92,000 | 106,000 | 110,500 |
Downloads
We'll help you choose the model and send you the technical documentation and a proposal.
Absorption chillers
Yazaki
Hot water-driven single-effect absorption chillers
Thermax
Hot water-driven single-effect absorption chillers
Thermax
Hot water-driven single-effect absorption chillers
Thermax
Steam-driven single-effect absorption chillers
Thermax
Steam-driven double-effect absorption chillers
Thermax
Gas-fired double-effect absorption chillers