Thermax
Thermax TAC L1
Hot water-driven single-effect absorption chillers
- Cooling capacity
- 157 – 1,000 kW
- Energy
- Hot water
- Efficiency
- COP: 0.7 to 0.8
Yazaki · Absorption chillers
Hot water-driven single-effect absorption chillers
Technical data
Models
Technical data from the manufacturer's data sheet.
| Model | Unit | WFC SC5 | WFC SC10 | WFC SC20 | WFC SC30 | WFC SC50 |
|---|---|---|---|---|---|---|
| GENERAL DATA | ||||||
| Version / application | Hot water-driven absorption chiller (single-effect H2O / LiBr) | |||||
| Installation location | Indoor / outdoor (weatherproof casing) | |||||
| Refrigerant / absorbent | Water (R718) / Lithium bromide (LiBr) | |||||
| Capacity control mode | On/off | |||||
| Chilled water inlet / outlet temperature | °C | 12.5 / 7.0 | ||||
| Cooling water inlet / outlet temperature (tower) | °C | 31.0 / 35.0 | ||||
| Generator hot water temperature range | °C | 70.0 to 95.0 (nominal: 88.0 / 83.0) | ||||
| Maximum allowable static pressure (all circuits) | kPa | 588 | ||||
| Maximum allowable static pressure (reference) | bar(g) | 5.88 | ||||
| Fouling factor | m²·K/kW | 0.086 | ||||
| CAPACITY AND CHILLED WATER CIRCUIT (EVAPORATOR) | ||||||
| Nominal cooling capacity | kW | 17.6 | 35.2 | 70.3 | 105 | 176 |
| Chilled water flow | l/s | 0.77 | 1.53 | 3.06 | 4.58 | 7.64 |
| Chilled water flow (reference) | m³/h | 2.77 | 5.51 | 11.02 | 16.49 | 27.5 |
| Evaporator pressure drop | kPa | 56 | 51 | 59.8 | 60.8 | 35.9 |
| Water volume | l | 8 | 17 | 47 | 73 | 120 |
| Chilled water tube section | DN | DN-32 | DN-40 | DN-50 | DN-65 | DN-80 |
| COOLING WATER CIRCUIT (ABSORBER / CONDENSER) | ||||||
| Heat to be rejected in cooling water | kW | 42.7 | 85.4 | 171 | 256 | 428 |
| Cooling water flow (tower) | l/s | 2.5 | 5.1 | 10.2 | 15.3 | 25.6 |
| Cooling water flow (reference) | m³/h | 9 | 18.36 | 36.72 | 55.08 | 92.16 |
| Absorber / condenser pressure drop | kPa | 41 | 85.3 | 45.3 | 46.4 | 37.4 |
| Water volume | l | 37 | 66 | 125 | 194 | 335 |
| Cooling water tube section | DN | DN-40 | DN-50 | DN-65 | DN-80 | DN-80 |
| HOT WATER CIRCUIT (GENERATOR) | ||||||
| Generator heat input | kW | 25.1 | 50.2 | 100 | 151 | 252 |
| Hot water flow | l/s | 1.2 | 2.4 | 4.8 | 7.2 | 12 |
| Hot water flow (reference) | m³/h | 4.32 | 8.64 | 17.28 | 25.92 | 43.2 |
| Generator pressure drop | kPa | 88 | 90.4 | 46.4 | 60.4 | 86.7 |
| Water volume | l | 10 | 21 | 54 | 84 | 170 |
| Hot water tube section | DN | DN-40 | DN-50 | DN-65 | DN-80 | DN-80 |
| ELECTRICAL DATA AND ACOUSTICS | ||||||
| Supply voltage | V / Hz | Single-phase 220V AC, 50Hz | ||||
| Nominal electrical consumption | W | 48 | 210 | 260 | 310 | 550 |
| Rated current | A | 0.23 | 0.43 | 0.92 | 1.25 | 4.74 |
| Sound power level | dB(A) | 46 | 49 | 52 | 54 | 58 |
| DIMENSIONS, WEIGHTS AND CASING | ||||||
| Width | mm | 594 | 760 | 1,060 | 1,380 | 1,780 |
| Depth | mm | 744 | 970 | 1,220 | 1,520 | 1,960 |
| Height (including mounting plates) | mm | 1,736 | 1,920 | 2,030 | 2,065 | 2,135 |
| Empty weight | kg | 365 | 500 | 930 | 1,450 | 2,400 |
| Operating weight (filled) | kg | 600 | 1,155 | 1,800 | 3,025 | 4,800 |
| Casing and exterior finish | Galvanised sheet steel, hot powder-coated in metallic silver | |||||
Downloads
We'll help you choose the model and send you the technical documentation and a proposal.
Absorption chillers
Thermax
Hot water-driven single-effect absorption chillers
Thermax
Hot water-driven single-effect absorption chillers
Thermax
Steam-driven single-effect absorption chillers
Thermax
Steam-driven double-effect absorption chillers
Thermax
Gas-fired double-effect absorption chillers
Thermax
Exhaust gas-driven double-effect absorption chillers