Ammonia-water (NH₃-H₂O) and lithium bromide (H₂O-LiBr) absorption thermodynamic cycles, and Type I and Type II absorption heat pumps.

LiBr-H₂O single-effect cycle

In the H₂O – LiBr system, water acts as the refrigerant and lithium bromide (LiBr) as the absorbent. The circuit operates under vacuum: the water evaporates at very low pressure and temperature and absorbs heat from the chilled water circuit.

The refrigerant evaporates at very low pressure and temperature to absorb heat from the circuit to be cooled. The water vapour produced is then absorbed by a concentrated lithium bromide solution.

Unlike the H₂O-NH₃ cycle, water is the refrigerant, so the operating conditions of the evaporator determine the range of cooling temperatures the system can produce.

Operating principle

Stage 1. Generator

The LiBr solution receives thermal energy. Heating separates the refrigerant water from the absorbent.

Stage 2. Condenser

The water vapour from the generator gives off heat to the heat rejection circuit and condenses.

Stage 3. Expansion

The liquid water’s pressure is reduced before it enters the evaporator.

Stage 4. Evaporator

At low pressure, the water evaporates at a low temperature and absorbs heat from the chilled water circuit, producing the cooling effect.

Stage 5. Absorber

The water vapour from the evaporator is absorbed by the lithium bromide solution. This process releases heat, which must be removed through the heat rejection circuit.

Stage 6. Solution pumping

The dilute solution is pumped back to the generator, raising its pressure to continue the cycle.

Stage 7. Concentrated solution return

The concentrated solution returns from the generator to the absorber, giving off heat to the dilute solution. This closes the cycle.

The main feature of the LiBr-H₂O cycle is that it produces chilled water using thermal energy as the main driving energy of the refrigeration cycle, reducing the need for the electricity associated with mechanical compression.

2.1. Single-effect LiBr-H₂O

In a single-effect configuration, the generator receives the driving thermal energy directly and there is a single main refrigerant generation stage.

This cycle can work with moderate-temperature heat sources, such as hot water (from 70 ºC), superheated water or certain waste heat sources, with a COP of around 0.7 – 0.8.

Its relatively simple configuration makes effective use of available heat sources when temperature conditions do not justify a double-effect cycle.

LiBr-H2O single-effect absorption cycle

LiBr-H₂O double-effect cycle

The double-effect cycle adds a second generation stage that makes more efficient use of the driving thermal energy.

The vapour produced in the first stage supplies thermal energy to a second generation stage, reducing the amount of external energy needed to produce the refrigerant.

This configuration achieves a higher thermal efficiency, with a COP of around 1.4 – 1.5, although it needs a higher-temperature driving source (steam, exhaust gas or direct gas firing).

The choice between single and double effect depends mainly on:

  • The temperature available from the heat source.
  • The cooling capacity required.
  • The operating profile.
  • The inlet and outlet temperatures of the circuits.
  • The conditions of the heat rejection circuit.
  • The overall energy efficiency of the installation.
  • LiBr-H2O double-effect absorption cycle

    Which technology suits your installation?

    We'll help you compare absorption, compression and cogeneration based on the energy available and the demand.

    Be the first to know

    Sign up for the latest news, exclusives and offers from Absorsistem

    To download the document, please enter your email address.

    Thank you! Your download has started.

    Something went wrong. Please try again later.

    Please check the highlighted fields.