Enerblue · High-efficiency chillers with natural refrigerant

Enerblue SILVER

Water chillers with inverter screw compressors and natural refrigerant

Cooling capacity
308 – 768 kW
Heating capacity
(up to 200 kW in DS version)
Efficiency
EER: 2.8 to 3.1
SEER: 4.3 to 4.6
Energy
Electricity
Ask an engineer
Enerblue SILVER

Technical data

Key data

Cooling capacity
308 – 768 kW
Heating capacity
(up to 200 kW in DS version)
Rating conditions
A35;W7
Energy
Electricity
Output temperature
from +20 ºC to -10 ºC
Refrigerant
R290 (propane)
Efficiency
EER: 2.8 to 3.1
SEER: 4.3 to 4.6
Energy class
ErP Ecodesign compliant

Main advantages

  • Semi-hermetic screw compressors with variable frequency drive, built for industrial durability
  • Maximum part-load efficiency with control from 25 to 100 %
  • High-efficiency, low-consumption EC axial fans
  • Isolated, soundproofed compressor enclosure with ATEX ventilation and R290 leak detector
  • Optional heat recovery unit

Models

Enerblue SILVER models

Technical data from the manufacturer's data sheet.

SILVER
Model Unit 300.1340.1350.2370.2410.2460.2540.2600.2650.2710.2770.2
COOLING (EN 14511-3:2022 VALUES) (A35;W7)
Nominal cooling capacity (1), (5) kW 308 343 353 373 409 458 538 597 651 712 768
Total power input in cooling (1), (5) kW 100 111 116 119 127 150 174 189 213 245 261
EER (1), (5) 3.08 2.96 3.18 3.13 3.22 3.05 3.09 3.16 3.06 2.91 2.94
ErP SEASONAL ENERGY INDICES (1 INVERTER VERSION)
SEER (water 7°C) (1) 4.41 4.16 4.22 4.26 4.65 4.51 4.9 4.78 4.73 4.82 4.84
Seasonal energy efficiency ηsc (1) % 173.3 163.5 165.8 167.4 183 181.4 193 188.2 186.2 190 190.5
SEPR HT (high-temp. process) (1) 5.3 5.4 5.53 5.27 5.67 5.53 5.52 5.59 5.55 5.5 5.52
ErP SEASONAL ENERGY INDICES (FULL INVERTER VERSION)
SEER (water 7°C) (1) 4.35 4.44 4.7 4.95 4.7 4.97 4.9 4.95 4.9
Seasonal energy efficiency ηsc (1) % 171 174.6 185 195 185 195.8 193 195 193
SEPR HT (high-temp. process) (1) 5.83 5.45 5.89 5.81 5.91 5.95 5.76 5.82 5.78
COOLING + HEATING (EN 14511 VALUES) (W7;W45) - DS VERSION (DESUPERHEATER)
Nominal heat output (DS recovery) (7) kW 54.8 59.6 62.2 62.7 68.1 88.3 98 101 112 132 145
Nominal cooling capacity (7) kW 309 344 354 374 410 462 542 599 655 716 773
Total power input (7) kW 101 115 112 119 127 150 174 190 213 244 260
TER (Total Efficiency Ratio) (7) 3.6 3.69 3.53 3.67 3.76 3.67 3.68 3.68 3.6 3.48 3.53
COOLING + HEATING (EN 14511 VALUES) (W7;W45) - DC VERSION (TOTAL RECOVERY)
Nominal heat output (DC recovery) (8) kW 394 442 445 470 512 688 587 747 821 939 1,000
Nominal cooling capacity (8) kW 298 337 335 358 393 447 526 565 616 713 762
Total power input (8) kW 97.1 106 112 114 119 164 141 184 207 228 242
TER (Total Efficiency Ratio) (8) 7.13 6.96 7.35 7.26 7.61 7.4 7.33 7.13 6.94 7.25 7.28
COMPRESSOR AND REFRIGERANT (R290)
Compressor type Semi-hermetic screw
No. of compressors / circuits No. / No. 1 / 1 1 / 1 2 / 2 2 / 2 2 / 2 2 / 2 2 / 2 2 / 2 2 / 2 2 / 2 2 / 2
Capacity control (min / max) % 50 / 100 50 / 100 25 / 100 25 / 100 25 / 100 25 / 100 25 / 100 25 / 100 25 / 100 25 / 100 25 / 100
R290 charge per circuit kg 20.8 13.0 20.8 13.0 13.9 19.5 / 14.7 13.9 19.9 19.9 20.9 20.9
EC AXIAL FANS AND USER-SIDE HEAT EXCHANGER
Fan type EC axial
No. of fans No. 6 8 6 8 8 10 8 12 12 12 12
Total air flow m³/h 147,688 197,665 147,688 197,665 197,665 197,665 245,956 295,734 295,734 295,734 295,734
User heat exchanger type Brazed plate
User water flow (A35;W7) (1) m³/h 52.9 58.9 60.7 64.1 70.3 78.8 92.6 102.6 112 122.3 132
Water pressure drop (1) kPa 8.1 20.7 9.8 22.9 16.3 20 21 19.8 22.9 20.1 22.3
  • Notes and reference conditions (Enerblue SILVER technical catalogue - p. 10):
  • (1) Outdoor air temperature 35 °C; evaporator water inlet-outlet temperature 12-7 °C.
  • (5) Values calculated in accordance with EN 14511-3:2022.
  • (7) DS version (desuperheater): evaporator water inlet-outlet temperature 12-7 °C; desuperheater water inlet-outlet temperature 40-45 °C (20 % partial recovery).
  • (8) DC version (total recovery): evaporator water inlet-outlet temperature 12-7 °C; condenser water inlet-outlet temperature 40-45 °C (100 % total recovery).

Downloads

Catalogues and data sheets

Is the Enerblue SILVER range right for your project?

We'll help you choose the model and send you the technical documentation and a proposal.

High-efficiency chillers with natural refrigerant

Other ranges in this family

Enerblue PURPLE

Enerblue

Enerblue PURPLE

High-efficiency air-to-water chillers for industrial processes, with on/off compressors and natural refrigerant

Cooling capacity
30.7 – 291 kW
Heating capacity
(up to 88 kW in DS version)
Energy
Electricity
Efficiency
EER: 2.7 to 3.1
SEPR: 2.8 to 3.9
Enerblue PURPLEi

Enerblue

Enerblue PURPLEi

High-efficiency air-to-water chillers with inverter compressors, EC fans and natural refrigerant

Cooling capacity
30.5 – 291 kW
Heating capacity
(up to 73 kW in DS version)
Energy
Electricity
Efficiency
EER: 2.8 to 3.1
SEER: 4.1 to 4.4
Enerblue PURPLE FC

Enerblue

Enerblue PURPLE FC

Air-to-water chillers with free cooling, on/off compressors and natural refrigerant

Cooling capacity
54 – 146 kW
Heating capacity
(up to 34 kW in DS version)
Energy
Electricity
Efficiency
EER: 2.7 to 2.8

Be the first to know

Sign up for the latest news, exclusives and offers from Absorsistem

To download the document, please enter your email address.

Thank you! Your download has started.

Something went wrong. Please try again later.

Please check the highlighted fields.