Skip to content

Robur · Absorption chillers

Robur GA ACF

Gas-fired absorption chillers

Cooling capacity
17.7 – 88.5 kW
Efficiency
GUE 71%
Energy
Natural gas or LPG
Ask an engineer
Robur GA ACF

Technical data

Key data

Cooling capacity
17.7 – 88.5 kW
Rating conditions
A35W7
Energy
Natural gas or LPG
Output temperature
Chilled water down to 3 ºC
Refrigerant
R717 (ammonia)
Efficiency
GUE 71%

Main advantages

  • Up to 86 % lower electricity consumption
  • Natural refrigerant, no fluorinated gases
  • Independent, modular operation
  • Low maintenance

Models

Robur GA ACF models

Technical data from the manufacturer's data sheet.

GA ACF
Model Unit StandardLow-noise
GENERAL DATA
Version / application Gas-fired absorption chiller with low electricity consumption
Refrigerant (natural, ammonia)
Exempt from the F-Gas regulation
Hydrogen allowed in gas blend (H2NG Hydrogen Ready) %
Electricity saving compared with an electric chiller %
COOLING MODE
Cooling capacity (outdoor 35°C / water outlet 7°C, A35W7) kW 17.7
Cooling capacity (outdoor 35°C / water outlet −5°C, A35W-5) kW
Heat input kW 25
GUE (gas utilisation efficiency) in cooling % 0.708
Minimum chilled water outlet temperature °C 3
Maximum chilled water inlet temperature °C 45
Minimum chilled water inlet temperature °C 8
Nominal chilled water flow l/h 2,770
Internal pressure drop at nominal flow bar 0.29
Maximum outdoor temperature °C 45
Minimum outdoor temperature °C 0
ELECTRICAL DATA
Supply voltage V 230
Supply type Single-phase
Frequency Hz 50
Electrical power input kW 0.82 0.87
Protection rating IP X5D
INSTALLATION DATA
Natural gas G20 consumption (nominal) m³/h 2.68
LPG G30/G31 consumption (nominal) kg/h 1.97
Sound pressure level Lp at 5 m (max.) dB(A) 57.6 53
Maximum water circuit working pressure bar 4
Water connection: type Female (F)
Water connection: thread in 1 1/4
Gas connection: type Female (F)
Gas connection: thread in 3/4
Dimensions: width mm 850
Dimensions: height mm 1,446 1,516
Dimensions: depth mm 1,256
Operating weight kg 360

Downloads

Catalogues and data sheets

Is the Robur GA ACF range right for your project?

We'll help you choose the model and send you the technical documentation and a proposal.

Absorption chillers

Other ranges in this family

Yazaki WFC-SC

Yazaki

Yazaki WFC-SC

Hot water-driven single-effect absorption chillers

Cooling capacity
17.6 – 176 kW
Energy
Hot water
Efficiency
COP: 0.7
Thermax TAC L1

Thermax

Thermax TAC L1

Hot water-driven single-effect absorption chillers

Cooling capacity
157 – 1,000 kW
Energy
Hot water
Efficiency
COP: 0.7 to 0.8
Thermax TAC L5

Thermax

Thermax TAC L5

Hot water-driven single-effect absorption chillers

Cooling capacity
714 – 5,764 kW
Energy
Hot water
Efficiency
COP: 0.7 to 0.8
Thermax TAC S1

Thermax

Thermax TAC S1

Steam-driven single-effect absorption chillers

Cooling capacity
404 – 7,385 kW
Energy
Steam
Efficiency
COP: 0.7 to 0.8
Thermax TAC S2

Thermax

Thermax TAC S2

Steam-driven double-effect absorption chillers

Cooling capacity
400 – 7,410 kW
Energy
Steam
Efficiency
COP: 1.3 to 1.5
Thermax TAC G2

Thermax

Thermax TAC G2

Gas-fired double-effect absorption chillers

Cooling capacity
401 – 4,969 kW
Energy
Natural gas or LPG
Efficiency
COP: 1.3 to 1.5