Enerblue · High-efficiency chillers with natural refrigerant

Enerblue PURPLE FC

Air-to-water chillers with free cooling, on/off compressors and natural refrigerant

Cooling capacity
54 – 146 kW
Heating capacity
(up to 34 kW in DS version)
Efficiency
EER: 2.7 to 2.8
Energy
Electricity
Ask an engineer
Enerblue PURPLE FC

Technical data

Key data

Cooling capacity
54 – 146 kW
Heating capacity
(up to 34 kW in DS version)
Rating conditions
A35;W7
Energy
Electricity
Output temperature
from +20 ºC to +7 ºC
Refrigerant
R290 (propane)
Efficiency
EER: 2.7 to 2.8
Energy class
ErP Ecodesign compliant

Main advantages

  • Integrated direct free-cooling system with coil and valve as standard
  • Drastic reduction in electricity consumption in winter and mid-season by cooling without running the compressors
  • Highly robust semi-hermetic reciprocating compressors with 2- or 4-step control
  • Isolated compressor module as standard, with ATEX safety system and R290 leak detector
  • Optional heat recovery unit

Models

Enerblue PURPLE FC models

Technical data from the manufacturer's data sheet.

PURPLE FC
Model Unit 30.132.134.135.140.145.150.155.160.175.135.2
CHILLER MODE COOLING (EN 14511) (A35; W12/7°C - 30% glycol)
Nominal cooling capacity (1) kW 54.6 59.2 65.6 73.2 81.2 89.1 98.6 104.3 117.3 129.2 146
Total power input (1)(2) kW 19.4 21 23.1 25.8 30.3 32.6 35.7 38.1 42.4 46.4 51.4
Water flow (1) m³/h 10.4 11.3 12.5 14 15.5 17 18.8 19.9 22.4 24.6 27.8
EER (1) 2.8 2.8 2.8 2.8 2.7 2.7 2.8 2.7 2.8 2.8 2.8
DIRECT FREE-COOLING MODE (outdoor air 5°C; inlet water 12°C)
Free-cooling capacity (5) kW 25.5 26.7 29.1 30.6 41.5 44.6 46.4 49 53.6 57.1 60.8
Water outlet temperature (5) °C 9.6 9.7 9.7 9.9 9.4 9.5 9.6 9.6 9.7 9.8 9.9
Total Free-Cooling Temperature (TFT) °C -0.5 -1.2 -1 -2.3 1.8 1.1 1.1 0.6 -0.3 -1.2 -2.6
COMPRESSOR AND REFRIGERANT (R290)
Compressor type Semi-hermetic
No. of compressors No. 1 1 1 1 1 1 1 1 1 1 2
Refrigerant circuits No. 1 1 1 1 1 1 1 1 1 1 2
Capacity stages No. 2 2 2 2 2 2 2 2 2 2 4
CONDENSER FANS AND USER-SIDE HEAT EXCHANGER
Fan type Axial
No. of fans No. 1 1 1 1 2 2 2 2 2 2 2
Fan power input kW 1.6 1.6 1.6 1.6 3.2 3.2 3.2 3.2 3.2 3.2 3.2
Fan current A 3.4 3.4 3.4 3.4 6.8 6.8 6.8 6.8 6.8 6.8 6.8
Total air flow m³/h 21,000 21,000 21,000 21,000 42,000 42,000 42,000 42,000 42,000 42,000 42,000
User heat exchanger type Plate
Water pressure drop (1) kPa 73 71 68 73 73 72 67 70 67 67 38
DESUPERHEATER (DS PARTIAL RECOVERY - OPTIONAL)
DS nominal heat output (4) kW 11.3 12.4 15 19.2 19.4 21.6 24.5 25 28.7 32.5 34.1
DS water flow m³/h 1.9 2.1 2.6 3.3 3.3 3.7 4.2 4.3 4.9 5.6 5.9
DS pressure drop kPa 7 8 8 12 8 9 11 9 11 11 10
HYDRAULIC MODULE, ACOUSTIC DATA (LN) AND DIMENSIONS
Available external pressure kPa 66 62 101 74 76 77 87 87 89 81 90
Buffer tank capacity l 250
Hydraulic connections inches 2" 2" 2" 2" 2" 2" 2" 2"1/2 2"1/2 2"1/2 2"1/2
Sound power level LN (3) dB(A) 82 82 82 82 84 84 84 84 86 86 86
Sound pressure level at 10 m LN (3) dB(A) 54 54 54 54 56 56 56 56 58 58 58
Length / width / height mm 2890 / 1208 / 2390 2890 / 1208 / 2390 2890 / 1208 / 2390 2890 / 1208 / 2390 5330 / 1208 / 2390 5330 / 1208 / 2390 5330 / 1208 / 2390 5330 / 1208 / 2390 5330 / 1208 / 2390 5330 / 1208 / 2390 5330 / 1208 / 2390
  • Notes and reference conditions (Enerblue PURPLE FC technical catalogue):
  • (1) Outdoor air temperature 35 °C; evaporator water inlet/outlet temperature 12/7 °C with 30 % glycol, in accordance with EN 14511.
  • (2) Total power is the sum of the power input of compressors and fans, in accordance with EN 14511.
  • (3) Lw: free-field sound power levels in accordance with ISO 3744. Lp measured at 10 m in free field.
  • (4) Evaporator water temperature 12/7 °C; desuperheater 40/45 °C.
  • (5) Outdoor air temperature 5 °C; evaporator water inlet temperature 12 °C, 30 % glycol, nominal flow rate.

Downloads

Catalogues and data sheets

Is the Enerblue PURPLE FC range right for your project?

We'll help you choose the model and send you the technical documentation and a proposal.

High-efficiency chillers with natural refrigerant

Other ranges in this family

Enerblue SILVER

Enerblue

Enerblue SILVER

Water chillers with inverter screw compressors and natural refrigerant

Cooling capacity
308 – 768 kW
Heating capacity
(up to 200 kW in DS version)
Energy
Electricity
Efficiency
EER: 2.8 to 3.1
SEER: 4.3 to 4.6
Enerblue PURPLE

Enerblue

Enerblue PURPLE

High-efficiency air-to-water chillers for industrial processes, with on/off compressors and natural refrigerant

Cooling capacity
30.7 – 291 kW
Heating capacity
(up to 88 kW in DS version)
Energy
Electricity
Efficiency
EER: 2.7 to 3.1
SEPR: 2.8 to 3.9
Enerblue PURPLEi

Enerblue

Enerblue PURPLEi

High-efficiency air-to-water chillers with inverter compressors, EC fans and natural refrigerant

Cooling capacity
30.5 – 291 kW
Heating capacity
(up to 73 kW in DS version)
Energy
Electricity
Efficiency
EER: 2.8 to 3.1
SEER: 4.1 to 4.4

Be the first to know

Sign up for the latest news, exclusives and offers from Absorsistem

To download the document, please enter your email address.

Thank you! Your download has started.

Something went wrong. Please try again later.

Please check the highlighted fields.