Enerblue · High-efficiency chillers with natural refrigerant

Enerblue PURPLEi

High-efficiency air-to-water chillers with inverter compressors, EC fans and natural refrigerant

Cooling capacity
30.5 – 291 kW
Heating capacity
(up to 73 kW in DS version)
Efficiency
EER: 2.8 to 3.1
SEER: 4.1 to 4.4
Energy
Electricity
Ask an engineer
Enerblue PURPLEi

Technical data

Key data

Cooling capacity
30.5 – 291 kW
Heating capacity
(up to 73 kW in DS version)
Rating conditions
A35;W7
Energy
Electricity
Output temperature
from +20 ºC to -10 ºC
Refrigerant
R290 (propane)
Efficiency
EER: 2.8 to 3.1
SEER: 4.1 to 4.4
Energy class
ErP Ecodesign compliant

Main advantages

  • Continuous modulation with inverter technology
  • EC axial fans as standard for maximum consumption reduction at part load
  • Hybrid configuration in 2 circuits
  • Isolated compressor module as standard, with ATEX safety system and R290 leak detector
  • Optional heat recovery unit

Models

Enerblue PURPLEi models

Technical data from the manufacturer's data sheet.

PURPLEi (12.1 to 45.1)

PURPLEi (12.1 to 45.1)
Model Unit 12.115.120.122.125.130.132.135.140.145.1
NOMINAL COOLING (EN 14511 VALUES) (A35; W12/7°C)
Nominal cooling capacity (1) kW 30.5 34.1 38.3 45.3 49 55.4 63.4 76.9 86.5 91.4
Total power input in cooling (1) kW 9.9 11 12.8 15.5 18 17.5 21.4 26.6 27.9 29.9
EER (1) 3.1 3.1 3 2.9 2.8 3.1 3 2.9 3.1 3.1
SEER (ErP seasonal efficiency, fan coil W7) (2) 4.1 4.2 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.2
SEMI-HERMETIC INVERTER COMPRESSOR AND REFRIGERANT (R290)
Compressor type Semi-hermetic reciprocating inverter
No. of compressors / circuits No. / No. 1 / 1
Capacity control (min / max) % 50 / 100
R290 charge per circuit kg 1.9 1.9 1.7 1.7 2.9 1.9 3.5 3.5 4.4 4.4
EC AXIAL FANS AND USER-SIDE HEAT EXCHANGER
Fan type EC axial
No. of fans No. 1 1 1 1 1 1 1 1 2 2
Fan power input kW 0.7 0.9 1 1.1 1.4 1.1 1.4 1.4 2.1 2.4
Fan current draw A 1.8 1.8 1.8 1.8 1.8 2.4 2.4 2.4 5 5
Total air flow m³/h 14,217 14,564 15,033 15,792 15,742 21,324 21,215 21,071 37,520 38,108
User heat exchanger type Single-circuit plate
User water flow (A35; W12/7) (1) l/h 5,257 5,875 6,604 7,803 8,443 9,546 10,930 13,250 14,910 15,750
Water pressure drop (1) kPa 38.5 30.6 37 31.9 39 37.2 41.1 41.2 44.9 40.5
DESUPERHEATER (20% DS PARTIAL RECOVERY - OPTIONAL)
DS heat exchanger type Plate
DS nominal heat output (3) kW 6 7.4 7.9 9.2 12 11.5 12.4 18.7 17 21.6
DS water flow (W40/45°C) (3) l/h 1,028 1,265 1,358 1,586 2,067 1,976 2,140 3,220 2,917 3,720
DS water pressure drop (3) kPa 2 3 3 5 7 5 8 11 6 9
HYDRAULIC MODULE, ACOUSTIC DATA (LN) AND DIMENSIONS
Available pump pressure kPa 183.2 183.2 166 149.2 148.3 153.4 140.2 131.8 165.6 163.4
Pump power input kW 1.28 1.28 1.28 1.28 1.35 1.35 1.35 1.35 1.73 1.73
Buffer tank capacity l 130 130 130 130 130 130 250 250 250 250
User hydraulic connections inches 1"1/2 1"1/2 1"1/2 1"1/2 2" 1"1/2 2" 2" 2" 2"
Sound power level LN (4) dB(A) 74 75 75 76 84 84 84 84 86 86
Sound pressure level at 1 m LN (5) dB(A) 57 58 58 59 66 66 66 66 68 68
Length / width / height mm 1950 / 950 / 2000 1950 / 950 / 2000 1950 / 950 / 2000 1950 / 950 / 2000 1950 / 950 / 2000 1874 / 1212 / 2338 1874 / 1212 / 2338 1791 / 1212 / 2338 2877 / 1214 / 2338 2877 / 1214 / 2338
Shipping weight kg 596 596 640 657 670 801 814 828 1,039 1,069
  • Notes and reference conditions (Enerblue PURPLEi technical catalogue - p. 7):
  • (1) Performance in accordance with EN 14511: outdoor air temp. 35 °C; evaporator water inlet/outlet temp. 12/7 °C.
  • (2) Performance in accordance with EN 14511 / EN 14825 for an average climate (Strasbourg), fan coil applications (W7), variable outlet water temp.
  • (3) Water inlet/outlet temp.: evaporator 12/7 °C; desuperheater 40/45 °C.
  • (4) Lw: free-field sound power values calculated in accordance with ISO 3744. Operating conditions (A35; W7 °C).
  • (5) Sound pressure values measured at 1 m in free field in accordance with ISO 3744. Operating conditions (A35; W7 °C).

PURPLEi (55.1 to 80.2)

PURPLEi (55.1 to 80.2)
Model Unit 55.160.175.135.240.245.255.260.275.280.2
NOMINAL COOLING (EN 14511 VALUES) (A35; W12/7°C)
Nominal cooling capacity (1) kW 110 116.3 128.2 153 168.8 183.6 222.8 240.3 267.7 291
Total power input in cooling (1) kW 37 40.1 44.8 53 55.2 60.5 75.9 84.2 94 103
EER (1) 3 2.9 2.9 2.9 3 3.1 2.9 2.9 2.8 2.8
SEER (ErP seasonal efficiency, fan coil W7) (2) 4.1 4.1 4.1 4.1 4.4 4.3 4.1 4.1 4.1 4.1
SEMI-HERMETIC INVERTER COMPRESSOR AND REFRIGERANT (R290)
Compressor type Semi-hermetic reciprocating
No. of compressors / circuits No. / No. 1 / 1 1 / 1 1 / 1 2 / 2 2 / 2 2 / 2 2 / 2 2 / 2 2 / 2 2 / 2
Capacity control (min / max) % 50 / 100 50 / 100 50 / 100 25 / 100 25 / 100 25 / 100 25 / 100 25 / 100 25 / 100 25 / 100
R290 charge per circuit kg 4.5 5.2 5.2 3.8 / 3.8 4.7 / 4.7 4.7 / 4.7 5.2 / 5.2 5.2 / 5.2 5.3 / 5.3 5.5 / 5.5
EC AXIAL FANS AND USER-SIDE HEAT EXCHANGER
Fan type EC axial
No. of fans No. 2 2 2 2 4 4 4 4 4 4
Fan power input kW 2.6 2.8 2.9 2.9 4.2 4.7 5.2 5.6 5.9 5.9
Fan current draw A 5 5 5 5 9.9 9.9 9.9 9.9 9.9 9.9
Total air flow m³/h 39,838 40,491 41,555 41,519 84,477 84,418 84,013 83,784 83,400 83,201
User heat exchanger type Single-circuit plate Single-circuit plate Single-circuit plate Dual-circuit plate Dual-circuit plate Dual-circuit plate Dual-circuit plate Dual-circuit plate Dual-circuit plate Dual-circuit plate
User water flow (A35; W12/7) (1) l/h 18,950 20,030 22,080 26,340 29,070 31,610 38,340 41,350 46,070 50,070
Water pressure drop (1) kPa 38.8 37.3 34 25.8 28.6 29.2 29.6 29.2 39.2 43.3
DESUPERHEATER (20% DS PARTIAL RECOVERY - OPTIONAL)
DS heat exchanger type Plate
DS nominal heat output (3) kW 26.5 31.7 35.5 43.7 40.3 33.9 50.5 57.7 64.8 73.2
DS water flow (W40/45°C) (3) l/h 4,563 5,456 6,110 7,516 5,838 6,937 8,684 9,918 11,146 12,594
DS water pressure drop (3) kPa 10 12 12 9 6 8.4 11.6 14.3 18.2 21.8
HYDRAULIC MODULE, ACOUSTIC DATA (LN) AND DIMENSIONS
Available pump pressure kPa 166.7 164 159.2 179.6 169.2 162.6 147.3 138.3 148.4 140.4
Pump power input kW 2.45 2.45 2.45 3 3 3 3 3 4 4
Buffer tank capacity l 250 250 250 250 450 450 450 450 450 450
User hydraulic connections inches 2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 2"1/2 3" 3" 3"
Sound power level LN (4) dB(A) 86 88 88 86 90 90 90 92 92 92
Sound pressure level at 1 m LN (5) dB(A) 68 70 70 68 70 70 70 72 72 72
Length / width / height mm 2877 / 1214 / 2338 2877 / 1214 / 2338 2877 / 1214 / 2338 2877 / 1214 / 2338 5320 / 1211 / 2338 5320 / 1211 / 2338 5320 / 1211 / 2338 5320 / 1211 / 2338 5320 / 1211 / 2338 5320 / 1211 / 2338
Shipping weight kg 1,110 1,117 1,124 1,265 1,794 1,882 2,002 2,026 2,063 2,124
  • Notes and reference conditions (Enerblue PURPLEi technical catalogue - p. 8):
  • (1) Performance in accordance with EN 14511: outdoor air temp. 35 °C; evaporator water inlet/outlet temp. 12/7 °C.
  • (2) Performance in accordance with EN 14511 / EN 14825 for an average climate (Strasbourg), fan coil applications (W7), variable outlet water temp.
  • (3) Water inlet/outlet temp.: evaporator 12/7 °C; desuperheater 40/45 °C.
  • (4) Lw: free-field sound power values calculated in accordance with ISO 3744. Operating conditions (A35; W7 °C).
  • (5) Sound pressure values measured at 1 m in free field in accordance with ISO 3744. Operating conditions (A35; W7 °C).

Downloads

Catalogues and data sheets

Is the Enerblue PURPLEi range right for your project?

We'll help you choose the model and send you the technical documentation and a proposal.

High-efficiency chillers with natural refrigerant

Other ranges in this family

Enerblue SILVER

Enerblue

Enerblue SILVER

Water chillers with inverter screw compressors and natural refrigerant

Cooling capacity
308 – 768 kW
Heating capacity
(up to 200 kW in DS version)
Energy
Electricity
Efficiency
EER: 2.8 to 3.1
SEER: 4.3 to 4.6
Enerblue PURPLE

Enerblue

Enerblue PURPLE

High-efficiency air-to-water chillers for industrial processes, with on/off compressors and natural refrigerant

Cooling capacity
30.7 – 291 kW
Heating capacity
(up to 88 kW in DS version)
Energy
Electricity
Efficiency
EER: 2.7 to 3.1
SEPR: 2.8 to 3.9
Enerblue PURPLE FC

Enerblue

Enerblue PURPLE FC

Air-to-water chillers with free cooling, on/off compressors and natural refrigerant

Cooling capacity
54 – 146 kW
Heating capacity
(up to 34 kW in DS version)
Energy
Electricity
Efficiency
EER: 2.7 to 2.8